Induced Voltage in Cable Shielding by Harmonics and Deficiencies in Installation Procedures

Tensión inducida en la pantalla de cables por armónicos y deficiencias en procedimientos de instalación

DOI:

https://doi.org/10.15446/sicel.v11.110009

Palabras clave:

insulation, induced voltages, shielding, Harmonics, grounding, limiting distance, Electric modeling, cables (en)
Modelamiento eléctrico, Tensión inducida, Cables, Blindaje, Aislamiento, Armónicos, Puesta a tierra, distancia límite (es)

Descargas

Autores/as

  • Oscar Arnulfo Quiroga Quiroga Universidad Industrial de Santander
  • José David Esparza Universidad Industrial de Santander
  • Iván David Serna Suárez Universidad Industrial de Santander

Insulated cables are widely used for the transportation, distribution, and end-use installations of electrical power. They are also essential for the grid interconnection of new generation systems based on renewable sources. These types of conductors mitigate electrical risks and increase the reliability of the networks. However, induced voltages in the cable shield are a determining factor in their performance, as a very high value can lead to insulation deterioration, breakdowns, risks to individuals, and malfunctioning of electrical installations. This article presents the behavior of induced voltage and current on the cable shield based on installation conditions and the effect of harmonics in the system. Simulation results show that induced voltage in the cable shield increases due to factors such as the presence of harmonics in the system and cable length. To control these induced voltages, the cable installation procedure must be improved, incorporating good practices for transposition and grounding. Thus, for example, it was found that in the presence of harmonics and supraharmonics the voltage induced in the cable shield increases up to nine (9) times compared to the base case of not having harmonics in the system, but if there is an adequate transposition and grounding, that voltage induced in the cable shield only increases three (3) times with respect to the base case.

Los cables aislados son muy utilizados para el transporte, la distribución y las instalaciones de uso final de la energía eléctrica. También son indispensables para la interconexión a la red eléctrica de los nuevos sistemas de generación basados en fuentes renovables. Con este tipo de conductores se mitigan riesgos eléctricos y se incrementa la confiabilidad de las redes. No obstante, las tensiones inducidas en la pantalla del cable son un factor determinante en su desempeño, ya que un valor muy elevado puede provocar el deterioro del aislamiento, averías, riesgos para las personas y mal funcionamiento de las instalaciones eléctricas. En este artículo se muestra el comportamiento de la tensión y la corriente inducida en la pantalla de un cable en función de sus condiciones de instalación y por efecto de armónicos en el sistema. Resultados obtenidos bajo simulación muestran que la tensión inducida en la pantalla de los cables aumenta por factores como la presencia de armónicos en el sistema y la longitud de cable. Para controlar esas tensiones inducidas se debe mejorar el procedimiento de instalación de los cables, con buenas prácticas de trasposición y puesta a tierra.

Referencias

O. A. Quiroga, J. Meléndez y S. Herraiz, «Fault causes analysis in feeders of power distribution networks.,» Renewable Energy and Power Quality Journal, vol. 1, nº 9, pp. 1269-1272, 2011.

D. Georgiev, P. Stanchev, Y. Kamenov y Y. Rangelov, «Modelling of Underground Cables : Sensitivity Analysis on the Precision of Parameters,» de 018 International Conference on High Technology for Sustainable Development (HiTech), Sofia, Bulgaria, 2018.

IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV, IEEE Std 575-2014 (Revision of IEEE Std 575-1988).

B. Akbal, «Determination of the sheath current of high voltage underground cable line by using statistical methods,» International Journal of Engineering Science and Computing, vol. 6, nº 3, pp. 2188-2192, 2016.

S. Czapp, K. Dobrzynski, J. Klucznik y Z. Lubosny, «Impact of configuration of earth continuity conductor on induced sheath voltages in power cables,» from 2016 International Conference on Information and Digital Technologies (IDT), Rzeszow, Poland, 2016.

CENTELSA, «Cables para media tensión,» 2008.

P. Ocłoń, M. Rerak, R. V. Rao, P. Cisek, A. Vallati, D. Jakubek y B. Rozegnał, «Multiobjective optimization of underground power cable systems,» Energy, Vols. %1 de %2215, Part B, 2021.

J. Meléndez, O. A. Quiroga y S. Herraiz, «Analysis of sequences of events for the characterisation of faults in power systems,» Electric Power Systems Research, nº 87, pp. 22-30, 2012.

Effects of current on human beings and livestock - Part 2: Special aspects, IEC 60479-2:2019 , 2019.

P. Maneepeth, P. Thararak, P. Jirapong y C. Karaaom, «Mitigation of Induced Currents and Overvoltages in Metallic Sheath of 115 kV Underground Cable Using Sheath Voltage Limiter and Parallel Ground Continuity Conductor,» de 2021 9th International Electrical Engineering Congress (iEECON), Pattaya, Thailand, 2021.

IEEE Guide for Working Procedures on Underground Transmission Circuits with Induced Voltage -- Corrigendum 1, IEEE Std 1727-2013/Cor 1-2015, 2015.

IEEE Guide for Safety in AC Substation Grounding, IEEE Std 80-2013 (Revision of IEEE Std 80-2000/ Incorporates IEEE Std 80-2013/Cor 1-2015), 2015.

R. Muratovic, E. Schmautzer, L. Fickert, R. Woschitz, H. Lugschitz, A. Machl, K. Reich, M. Klein y G. Svejda, «Mutual inductive interference of 400 kV cable systems,» e & i Elektrotechnik und Informationstechnik, nº 134, p. 37–45, 2017.

C. K. Jung, J. B. Lee, J. W. Kang, X. H. Wang y Y. H. Song, «Sheath current characteristic and its reduction on underground power cable system,» de IEEE Power Engineering Society General Meeting, San Francisco, CA, USA, 2005.

M. Shaban, M. A. Salam, S. P. Ang, M. A. B. Sidik, Z. Buntat y W. Voon, «Assessing induced sheath voltage in multi-circuit cables: Revising the methodology,» de IEEE Conference on Energy Conversion (CENCON), Johor Bahru, 2015.

Y. Du, X. H. Wang y Z. H. Yuan, «Induced Voltages and Power Losses in Single-Conductor Armored Cables,» IEEE Transactions on Industry Applications, vol. 45, nº 6, pp. 2145-2151, 2009.

Z. Rashid, «Calculation of overhead and underground cable parameters at harmonic frequencies,» Electrical Engineering, nº 103, p. 729–741, 2021.

T. Kangro, J. Kilter, J. D. Silva y K. Tuttelberg, «Assessment of HV XLPE Cable Sheath Layer Modelling Approaches for EMT Studies,» de IEEE 59th International Scientific Conference on Power and Electrical Engineering of Riga Technical University (RTUCON), Riga, Latvia, 2018.

J. YONG, B. Xia, H. Yong, W. Xu, N. Alexandre y T. C. Hartman, «Harmonic Voltage Induction on Pipelines: Measurement Results and Methods of Assessment,» de IEEE Power & Energy Society General Meeting (PESGM), Portland, OR, USA, 2018.

J. Plotkin, D. Schulz y R. Hanitsch, «Influence of Long High Voltage Cables on Total Harmonic Distortion of Currents in Wind Farms,» from IECON 2006 - 32nd Annual Conference on IEEE Industrial Electronics, Paris, France, 2006.

U. S. Gudmundsdottir, J. De Silva, C. L. Bak y W. Wiechowski, «Double layered sheath in accurate HV XLPE cable modeling,» from IEEE PES General Meeting, Minneapolis, MN, USA, 2010.

M. Santos y M. A. Calafat, «Dynamic simulation of induced voltages in high voltage cable sheaths: Steady state approach,» International Journal of Electrical Power and Energy Systems, vol. 105, pp. 1-16, 2019.

A. N. Gusev, A. A. Antonov, D. V. Dvorkin y M. S. Volkov, «Case studies for optimal cable line placement and sheath grounding to increase its operational characteristics,» from RTUCON-2020 – International Scientific Conference on Electrical and Power Engineering, Riga, Latvia, 2020.

Cómo citar

APA

Quiroga Quiroga, O. A., Esparza, J. D. y Serna Suárez, I. D. (2024). Induced Voltage in Cable Shielding by Harmonics and Deficiencies in Installation Procedures . Simposio Internacional sobre la Calidad de la Energía Eléctrica - SICEL, 11. https://doi.org/10.15446/sicel.v11.110009

ACM

[1]
Quiroga Quiroga, O.A., Esparza, J.D. y Serna Suárez, I.D. 2024. Induced Voltage in Cable Shielding by Harmonics and Deficiencies in Installation Procedures . Simposio Internacional sobre la Calidad de la Energía Eléctrica - SICEL. 11, (ene. 2024). DOI:https://doi.org/10.15446/sicel.v11.110009.

ACS

(1)
Quiroga Quiroga, O. A.; Esparza, J. D.; Serna Suárez, I. D. Induced Voltage in Cable Shielding by Harmonics and Deficiencies in Installation Procedures . SICEL 2024, 11.

ABNT

QUIROGA QUIROGA, O. A.; ESPARZA, J. D.; SERNA SUÁREZ, I. D. Induced Voltage in Cable Shielding by Harmonics and Deficiencies in Installation Procedures . Simposio Internacional sobre la Calidad de la Energía Eléctrica - SICEL, [S. l.], v. 11, 2024. DOI: 10.15446/sicel.v11.110009. Disponível em: https://revistas.unal.edu.co/index.php/SICEL/article/view/110009. Acesso em: 7 feb. 2025.

Chicago

Quiroga Quiroga, Oscar Arnulfo, José David Esparza, y Iván David Serna Suárez. 2024. «Induced Voltage in Cable Shielding by Harmonics and Deficiencies in Installation Procedures ». Simposio Internacional Sobre La Calidad De La Energía Eléctrica - SICEL 11 (enero). https://doi.org/10.15446/sicel.v11.110009.

Harvard

Quiroga Quiroga, O. A., Esparza, J. D. y Serna Suárez, I. D. (2024) «Induced Voltage in Cable Shielding by Harmonics and Deficiencies in Installation Procedures », Simposio Internacional sobre la Calidad de la Energía Eléctrica - SICEL, 11. doi: 10.15446/sicel.v11.110009.

IEEE

[1]
O. A. Quiroga Quiroga, J. D. Esparza, y I. D. Serna Suárez, «Induced Voltage in Cable Shielding by Harmonics and Deficiencies in Installation Procedures », SICEL, vol. 11, ene. 2024.

MLA

Quiroga Quiroga, O. A., J. D. Esparza, y I. D. Serna Suárez. «Induced Voltage in Cable Shielding by Harmonics and Deficiencies in Installation Procedures ». Simposio Internacional sobre la Calidad de la Energía Eléctrica - SICEL, vol. 11, enero de 2024, doi:10.15446/sicel.v11.110009.

Turabian

Quiroga Quiroga, Oscar Arnulfo, José David Esparza, y Iván David Serna Suárez. «Induced Voltage in Cable Shielding by Harmonics and Deficiencies in Installation Procedures ». Simposio Internacional sobre la Calidad de la Energía Eléctrica - SICEL 11 (enero 30, 2024). Accedido febrero 7, 2025. https://revistas.unal.edu.co/index.php/SICEL/article/view/110009.

Vancouver

1.
Quiroga Quiroga OA, Esparza JD, Serna Suárez ID. Induced Voltage in Cable Shielding by Harmonics and Deficiencies in Installation Procedures . SICEL [Internet]. 30 de enero de 2024 [citado 7 de febrero de 2025];11. Disponible en: https://revistas.unal.edu.co/index.php/SICEL/article/view/110009

Descargar cita

CrossRef Cited-by

CrossRef citations0

Dimensions

PlumX

Visitas a la página del resumen del artículo

92

Descargas

Los datos de descargas todavía no están disponibles.