Publicado

2026-04-15

Impacto Dinámico del Arranque de Sistemas de Bombeo en Red de Media Tensión: Caso de Estudio en Cultivo de Arroz

Dynamic Impact of Pumping System Start-up on Medium Voltage Grids: Rice Cultivation Case Study

DOI:

https://doi.org/10.15446/sicel.v12.121184

Palabras clave:

Arranque de Motores, Huecos de Tensión, Compensación de Potencia Reactiva, Arrancador Suave (es)
motor startup, voltage sags, reactive power compensation, soft starters (en)

Descargas

Autores/as

  • ULISES MANASSERO UNIVERSIDAD TECNOLOGICA NACIONAL - CENTRO DE INVESTIGACIÓN EN INGENIERIA ELÉCTRICA Y SISTEMAS ENERGÉTICOS (CIESE) 0000-0003-4844-6362
  • Ariel Loyarte UTN-FRSF
  • Pablo Marelli UTN-FRSF
  • Nicolas Pochettino UTN-FRSF
  • Javier Acosta UTN-FRSF

Este trabajo analiza el arranque secuencial de un sistema de bombeo para riego de arroz (GU PILAGA) y su impacto en la red de distribución de media tensión operada por EPE-SF. Se modelan dos escenarios operativos—riego normal y exceso de lluvias—considerando el comportamiento eléctrico en estado estacionario y transitorio. Se realizan simulaciones dinámicas con arrancadores suaves y compensación reactiva. Los resultados demuestran factibilidad técnica sin sags relevantes en la red de media tensión. Las barras de baja tensión presentan eventos transitorios mitigables mediante ajustes de tap y bancos de capacitores. Se proponen medidas de optimización.

This paper analyzes the sequential startup of a pumping system for rice irrigation (GU PILAGA) and its impact on the medium-voltage distribution network operated by EPE-SF. Two operational scenarios—normal irrigation and excess rainfall— are modeled, including electrical steady-state and transient behavior. Dynamic simulations are conducted with soft starters and reactive compensation. Results show technical feasibility, with no significant voltage sags in the utility grid. Low-voltage nodes experience transient issues that can be mitigated by tap adjustments and capacitor banks. Recommendations for optimization are discussed.

Descargas

Los datos de descargas todavía no están disponibles.

Citas

[1] A. R. R. S. de Oliveira, P. M. de Oliveira, y L. C. P. da Silva, "Analysis of voltage sag caused by induction motor starting in industrial power systems," en IEEE Industry Applications Society Annual Meeting, 2021, pp. 1-8.

[2] M. H. B. M. Shariff, M. F. N. Khan, y J. A. M. Jona, "A review on voltage sag analysis and mitigation for sensitive industrial equipment," Energies, vol. 14, n.º 21, p. 7255, 2021.

[3] F. B. G. de Souza, J. V. M. de Carvalho, y W. C. de Souza, "Dy-namic modeling of induction motors and their impact on power quality of weak distribution networks," Electric Power Systems Research, vol. 189, p. 106601, 2020.

[4] IEEE Recommended Practice for Monitoring Electric Power Quality, IEEE Std 1159-2019, 2019.

[5] S. D. G. de S. Filho, R. P. T. Bascopé, y A. L. Batschauer, "Com-patibility analysis between voltage sags and industrial equip-ment based on the ITIC curve," IEEE Latin America Transactions, vol. 15, n.º 8, pp. 917-924, 2017.