Impact Analysis of Asymmetric Conditions on an Oil-Filled Distribution Transformer Performance
Palabras clave:
Aging factor, demand profile, hot spot, load unbalance, loss of life, phase displacement, thermal-electrical model (es)Descargas
This paper shows the results obtained from the simulation of a study case about the impact of asymmetric operational conditions on oil-filled distribution transformer useful life. The results depend on the supplied energy level through three different demand profiles (unbalance) mixed with two asymmetric conditions (no asymmetric condition and two additional cases with different asymmetric conditions). The disturbance analysis is realized through the FBD and symmetrical components theories, in order to obtain an equivalent factor to the , which will be used to characterize the transformer loss of life from the temperature rise in the transformer (oil). Finally, it is realized a discussion about the results obtained and the possible analysis field for future studies of this topic (asymmetric conditions).
Cómo citar
APA
Mazo Mantilla, H. F. (2015). Impact Analysis of Asymmetric Conditions on an Oil-Filled Distribution Transformer Performance. Simposio Internacional sobre la Calidad de la Energía Eléctrica - SICEL, 8. https://revistas.unal.edu.co/index.php/SICEL/article/view/52135
ACM
[1]
Mazo Mantilla, H.F. 2015. Impact Analysis of Asymmetric Conditions on an Oil-Filled Distribution Transformer Performance. Simposio Internacional sobre la Calidad de la Energía Eléctrica - SICEL. 8, (ene. 2015).
ACS
(1)
Mazo Mantilla, H. F. Impact Analysis of Asymmetric Conditions on an Oil-Filled Distribution Transformer Performance. SICEL 2015, 8.
ABNT
MAZO MANTILLA, H. F. Impact Analysis of Asymmetric Conditions on an Oil-Filled Distribution Transformer Performance. Simposio Internacional sobre la Calidad de la Energía Eléctrica - SICEL, [S. l.], v. 8, 2015. Disponível em: https://revistas.unal.edu.co/index.php/SICEL/article/view/52135. Acesso em: 10 feb. 2025.
Chicago
Mazo Mantilla, Harold Francisco. 2015. «Impact Analysis of Asymmetric Conditions on an Oil-Filled Distribution Transformer Performance». Simposio Internacional Sobre La Calidad De La Energía Eléctrica - SICEL 8 (enero). https://revistas.unal.edu.co/index.php/SICEL/article/view/52135.
Harvard
Mazo Mantilla, H. F. (2015) «Impact Analysis of Asymmetric Conditions on an Oil-Filled Distribution Transformer Performance», Simposio Internacional sobre la Calidad de la Energía Eléctrica - SICEL, 8. Disponible en: https://revistas.unal.edu.co/index.php/SICEL/article/view/52135 (Accedido: 10 febrero 2025).
IEEE
[1]
H. F. Mazo Mantilla, «Impact Analysis of Asymmetric Conditions on an Oil-Filled Distribution Transformer Performance», SICEL, vol. 8, ene. 2015.
MLA
Mazo Mantilla, H. F. «Impact Analysis of Asymmetric Conditions on an Oil-Filled Distribution Transformer Performance». Simposio Internacional sobre la Calidad de la Energía Eléctrica - SICEL, vol. 8, enero de 2015, https://revistas.unal.edu.co/index.php/SICEL/article/view/52135.
Turabian
Mazo Mantilla, Harold Francisco. «Impact Analysis of Asymmetric Conditions on an Oil-Filled Distribution Transformer Performance». Simposio Internacional sobre la Calidad de la Energía Eléctrica - SICEL 8 (enero 1, 2015). Accedido febrero 10, 2025. https://revistas.unal.edu.co/index.php/SICEL/article/view/52135.
Vancouver
1.
Mazo Mantilla HF. Impact Analysis of Asymmetric Conditions on an Oil-Filled Distribution Transformer Performance. SICEL [Internet]. 1 de enero de 2015 [citado 10 de febrero de 2025];8. Disponible en: https://revistas.unal.edu.co/index.php/SICEL/article/view/52135
Descargar cita
Visitas a la página del resumen del artículo
192
Descargas
Los datos de descargas todavía no están disponibles.