The effects on radial distribution networks caused by replacing incandescent lamps with compact fluorescent lamps and LEDs

Efectos sobre los circuitos de distribución causados por el reemplazo de lámparas incandescentes con bombillas fluorescentes compactas y LEDs

DOI:

https://doi.org/10.15446/ing.investig.v31n2SUP.25219

Keywords:

compact fluorescent lamps (CFLs), lightemitting diodes (LEDs), harmonic distortion, power quality (en)
Bombillas fluorescentes compactas (BFCs), diodos emisores de luz de alta potencia (LEDs), distorsión armónica, calidad de la potencia (es)

Downloads

Authors

  • Ana María Blanco Castañeda Tecnische Universität Dresden
  • Estrella Esperanza Parra Universidad Nacional de Colombia

Compact fluorescent lamps and high-power light-emitting diodes use an electronic device that injects harmonics into distribution networks, thereby altering power quality levels. This paper shows these lamps' electrical characterisation and the results of a computer simulation of a radial distribution feeder supplying electricity to customers who use this type of harmonic load. The objective was to analyse the effect on distribution systems due to CFLs and LEDs' high penetration.

Las bombillas fluorescentes compactas y los diodos emisores de luz de alta potencia usan un dispositivo electrónico que inyecta armónicos en las redes de distribución, alterando los índices de calidad de la potencia. Este artículo muestra la caracterización eléctrica de este tipo de lámparas y el resultado de la simulación de un circuito de distribución radial que alimenta a consumidores residenciales que utilizan este tipo de cargas armónicas. El objetivo es el de analizar el efecto en los sistemas de distribución debido a la alta penetración de BFCs y LEDs.

References

Acevedo, I. L; Morgan, G. and Morgan, F. ''The Transition to Solid-State Lighting'' Procedigs of the IEEE, vol. 97, no. 3, pp.481-510, Mar. 2009.

Blanco, A.M. "Efecto sobre los circuitos de distribución secundarios debido al uso intensivo de Bombillas Fluorescentes Compactas y LEDs (Light Emitting Diodes),'' M.Sc. dissertation, Dept. of Electrical Eng., National University of Colombia, Bogotá, 2010.

Blanco, A.M; Parra, E. ''Effects of High Penetration of CFLs and LEDs on the Distribution Networks,'' in the 14th International Conference on Harmonics and Quality of Power 2010, pp.1-5

Cunill-Solà J. and Salichs, M. ''Study and Characterization of Waveforms from Low-Watt (<25W) Compact Fluorescent Lamps with Electronic Ballasts,'' IEEE Trans. Power Delivery, vol. 22, no. 4, pp 2305-2311, Oct. 2007.

IEC Standard Self-ballasted lamps for general lighting services - Performance requirements, IEC Standard 60969, Mar. 2001.

IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, IEEE Standard 519-1992, Apr. 1993.

IESNA, Approved thod for the electrical and photometric measurements of single -ended Compact Fluorescent Lamps, IESNA Standard LM-66-00. 2000

Nassif A.B. and Acharya, J. ''An Investigation on the Harmonic Attenuation Effect of Modern Compact Fluorescent Lamps,'' in the 13th International Conference on Harmonics and Quality of Power 2008, pp.1-6.

Watson, N. R; Scott, T. and Hirsch, S. ''Implications for Distribution Networks of High Penetration of Compact Fluorescent Lamps,'' IEEE Trans. Power Delivery, vol. 24, No. 3, pp. 1521-1528, July 2009.