Grade-two resistance screw shear connector behaviour for a composite section system

Comportamiento de conectores de cortante tipo tornillo de resistencia grado dos para un sistema de sección compuesta

DOI:

https://doi.org/10.15446/ing.investig.v28n2.14886

Keywords:

shear connector, push-out test, non-linear analysis (en)
conectores de cortante, ensayos push-out, análisis no lineal (es)

Authors

  • Maritzabel Molina Herrera .
  • Dorian Luis Linero S. Universidad Nacional de Colombia
  • Xavier Fernando Hurtado A. Universidad Nacional de Colombia

Screw shear connectors have been most commonly used in Colombia for many years; however, there is no current design methodology justifying its use in composite sections and prevailing rules insist that elements used as shear connectors must be tested. Along with the usual details of bending design and vertical shear, horizontal shear design on the composite section interface must be specified, even more so in adjusting such design to Colombian construction. A study was thus undertaken analysing effects on composite sections when screws were used as shear connectors. This research studied 18 composite section models having two 21MPa concrete slabs which had different configurations with one, two or three 1/2", 5/8" or 3/4" diameter shear connector type screws, and 0.08m, 0.12m or 0.14m separations. Three specimens were tested for each model by direct shear or push-out method. The corresponding analysis was done according to laboratory results, assessing the influence of diameter and connector separation on the model’s behavior; screw design in composite sections was then formulated. A model of the tests was analysed using a finite element method based-programme which reviewed in detail those aspects which had little appreciable effect on the physical tests, including concrete degradation in the interface section.

En Colombia, desde hace muchos años, uno de los tipos de conectores de cortante más usados son los tornillos, pero en la actualidad no existe ninguna metodología de diseño que justifique su uso en elementos de sección compuesta, y la normatividad vigente indica que hay que realizar ensayos de los elementos que se pretendan emplear como conectores. Junto con los habituales detalles para diseño a flexión, y cortante vertical, es necesario especificar el diseño para el cortante horizontal generado en la interfase de la sección compuesta, y más aún, ajustar el diseño para las condiciones locales de construcción colombiana. Con esta finalidad se desarrolló un estudio en el cual se analizan los diversos efectos producidos en las secciones compuestas cuando se emplean tornillos como conectores de cortante. En esta investigación se estudiaron 18 modelos de sección compuesta fabricadas con perfiles de alma llena y losas de concreto de 21 MPa, en las cuales se manejaron configuraciones de 1, 2 ó 3 conectores de cortante tipo tornillo con diámetros de 1/2”, 5/8” ó 3/4"; y para separaciones de 0.08 m, 0.12 m o 0.14 m, por cada modelo se ensayaron tres probetas ante solicitación de corte directo (push-out). De acuerdo con los resultados obtenidos en laboratorio, se efectuó el análisis correspondiente, evaluando la incidencia del diámetro y la separación de los conectores, en el comportamiento de los modelos, para posteriormente plantear una formulación de su diseño en secciones compuestas. Paralelamente, se analiza un modelo de los ensayados por medio de un programa que emplea el método de los elementos finitos, con el cual se pretende revisar en detalle aspectos poco apreciables en los ensayos físicos, entre ellos la degradación del concreto en la interfaz de la sección.

References

Asociación de Ingeniería Sísmica., NSR-98., TOMO 3, Bogotá, 1998, pp. F38-F39.

Chinn, J., Push-out tests on lightweight composite slabs., Engineering Journal, AISC, 1965, pp. 129-134.

Davies, C., Small-scale push-out tests on welded stud shear connectors., Concrete, 1967, pp. 311-316.

Hurtado, X., Comportamiento de conectores tipo tornillo grado dos para un sistema de sección compuesta con concreto de 21MPa ante solicitación de corte directo., Tesis presentada a la Universidad Nacional de Colombia, para optar por el título de Magíster en Ingeniería-Estructuras, 2007.

Johnson, R., Oehlers, D., Analysis and design for longitudinal shear in composite t-beams., Proc. Instn. Civ. Engrs, Part 2, 1981, pp. 989-1021. DOI: https://doi.org/10.1680/iicep.1981.1735

Lam, D., Behavior of headed stud shear connectors in composite beam., Journal of Structural Engineering, ASCE, 2005, pp. 96-107. DOI: https://doi.org/10.1061/(ASCE)0733-9445(2005)131:1(96)

Oehlers, J., Composite beams with limited-slip-capacity shear connectors., Journal of Structural Engineering, ASCE, 1995, pp. 932-938. DOI: https://doi.org/10.1061/(ASCE)0733-9445(1995)121:6(932)

Ollgaard, J., Slutter, R., Fisher, J., Shear strength of stud connectors in lightweight and normal-weight concrete., Engineering Journal, AISC, 1971, pp. 55-64.

Slutter, R., Driscoll, G., Flexural strength of steel-concrete composite beams., J. Struct. Div.,91, 1965, pp. 71-99. Viest, I., Investigation of stud shear connectors for composite concrete and steel t-beams., Journal. of the American Concrete Institute, ACI, 1956, pp. 875-890. DOI: https://doi.org/10.1061/JSDEAG.0001257

William, K., Warnke, E., Constitutive model for the tiaxial behavior of concrete., Proceedings International

Association for Bridge and Structural Engineering, 1975, pp. 174.

How to Cite

APA

Molina Herrera, M., Linero S., D. L. and Hurtado A., X. F. (2008). Grade-two resistance screw shear connector behaviour for a composite section system. Ingeniería e Investigación, 28(2), 4–14. https://doi.org/10.15446/ing.investig.v28n2.14886

ACM

[1]
Molina Herrera, M., Linero S., D.L. and Hurtado A., X.F. 2008. Grade-two resistance screw shear connector behaviour for a composite section system. Ingeniería e Investigación. 28, 2 (May 2008), 4–14. DOI:https://doi.org/10.15446/ing.investig.v28n2.14886.

ACS

(1)
Molina Herrera, M.; Linero S., D. L.; Hurtado A., X. F. Grade-two resistance screw shear connector behaviour for a composite section system. Ing. Inv. 2008, 28, 4-14.

ABNT

MOLINA HERRERA, M.; LINERO S., D. L.; HURTADO A., X. F. Grade-two resistance screw shear connector behaviour for a composite section system. Ingeniería e Investigación, [S. l.], v. 28, n. 2, p. 4–14, 2008. DOI: 10.15446/ing.investig.v28n2.14886. Disponível em: https://revistas.unal.edu.co/index.php/ingeinv/article/view/14886. Acesso em: 13 jul. 2024.

Chicago

Molina Herrera, Maritzabel, Dorian Luis Linero S., and Xavier Fernando Hurtado A. 2008. “Grade-two resistance screw shear connector behaviour for a composite section system”. Ingeniería E Investigación 28 (2):4-14. https://doi.org/10.15446/ing.investig.v28n2.14886.

Harvard

Molina Herrera, M., Linero S., D. L. and Hurtado A., X. F. (2008) “Grade-two resistance screw shear connector behaviour for a composite section system”, Ingeniería e Investigación, 28(2), pp. 4–14. doi: 10.15446/ing.investig.v28n2.14886.

IEEE

[1]
M. Molina Herrera, D. L. Linero S., and X. F. Hurtado A., “Grade-two resistance screw shear connector behaviour for a composite section system”, Ing. Inv., vol. 28, no. 2, pp. 4–14, May 2008.

MLA

Molina Herrera, M., D. L. Linero S., and X. F. Hurtado A. “Grade-two resistance screw shear connector behaviour for a composite section system”. Ingeniería e Investigación, vol. 28, no. 2, May 2008, pp. 4-14, doi:10.15446/ing.investig.v28n2.14886.

Turabian

Molina Herrera, Maritzabel, Dorian Luis Linero S., and Xavier Fernando Hurtado A. “Grade-two resistance screw shear connector behaviour for a composite section system”. Ingeniería e Investigación 28, no. 2 (May 1, 2008): 4–14. Accessed July 13, 2024. https://revistas.unal.edu.co/index.php/ingeinv/article/view/14886.

Vancouver

1.
Molina Herrera M, Linero S. DL, Hurtado A. XF. Grade-two resistance screw shear connector behaviour for a composite section system. Ing. Inv. [Internet]. 2008 May 1 [cited 2024 Jul. 13];28(2):4-14. Available from: https://revistas.unal.edu.co/index.php/ingeinv/article/view/14886

Download Citation

CrossRef Cited-by

CrossRef citations0

Dimensions

PlumX

Article abstract page views

524

Downloads

Download data is not yet available.